In order to best meet client's needs, all of our operations are strictly performed in line with our motto "High Quality, Competitive Price, Fast Service" for Timer Relay Switch, Thermal Relay Switch, Time Delay Of Contactor, Striving hard to attain continual success based on quality, reliability, integrity, and complete understanding of market dynamics.
Renewable Design for Vacuum Contactor Switch - Siemens Type AC Contactor J3TF – JUHONG Detail:

Type J3TF-9/12 J3TF-16/22 J3TF-32 J3TF-45/63 J3TF-75/85 J3TF-110/140 J3TF-170/205 J3TF-250/300 J3TF-400/475
Mechanical
Endurance(X106)
10 10 10 8 8 8 8 8 8
Conventional
thermal current(A)
20 30 45 80 100 160 210 300 400/550
Rated insulation
voltage(V)
660 660 660 1000 1000 1000 1000 1000 1000
Rated operating
current(A)
AC-3 9/12 16/22 32 45/63 75/85 110/140 170/205 250/300 400/475
AC-4 3.3/4.3 7.7/8.5 15.6 24/28 34/42 54/68 75/96 110/125 150
Power of controllablemotor(KW) AC-3 380V 4/5.5 7.5/11 15 22/30 37/45 55/75 90/110 132/160 200/250
660V 5.5/7.5 11 23 39/55 67 100 156 235 375
Power of controllablemotor(KW) AC-4 380V 1.4/1.9 3.5/4 7.5 12/14 17/21 27/35 38/50 58/66 81
660V 2.4/3.3 6/6.6 13 20.8/24 29.5/36 46.9/60 66/86 100/114 140
Frequency of operation
(I/h)
AC-3 1000 750 750 1200/1000 1000/850 1000/750 700/500 700/500 500/420
AC-4 250 250 250 400/300 300/250 300/200 200/130 200/130 150
Electrical
endurance
(X106)
AC-3 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.2
AC-4 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2
Operating voltage
range of coil
(0.8-1.1)Ue
Power
consumption of coil
Atracting
(VA)
10 10 12.1 17 32 39 58 84 115
Starting
(VA)
68 69 101 183 330 550 910 1430 2450
Rated insulation voltageof auxiliary contacts(V) 690 690 690 690 690 690 690 690 690 690
Conventional thermal currentof auxiliary contacts(A) 10 10 10 10 10 10 10 10 10 10
Rated operating currentof auxiliary contacts(A) AC15
380/220
6/10 6/10 4/6 4/6 4/6 4/6 4/6 4/6 4/6
DC13
220v
0.45 0.45 0.45 0.45 0.45 0.45 0.45 0.45 0.45
Rated voltage
of the control
coil(V)
50HZ 24 36 48 110 127 220 380,etc
60HZ 24 110 220 440 etc

Product detail pictures:

Renewable Design for Vacuum Contactor Switch - Siemens Type AC Contactor J3TF – JUHONG detail pictures

Renewable Design for Vacuum Contactor Switch - Siemens Type AC Contactor J3TF – JUHONG detail pictures

Renewable Design for Vacuum Contactor Switch - Siemens Type AC Contactor J3TF – JUHONG detail pictures

Renewable Design for Vacuum Contactor Switch - Siemens Type AC Contactor J3TF – JUHONG detail pictures

Renewable Design for Vacuum Contactor Switch - Siemens Type AC Contactor J3TF – JUHONG detail pictures


Related Product Guide:

Quality First,and Customer Supreme is our guideline to provide the best service to our customers.Nowadays, we are trying our best to become one of the best exporters in our field to meet customers more need for Renewable Design for Vacuum Contactor Switch - Siemens Type AC Contactor J3TF – JUHONG , The product will supply to all over the world, such as: Lebanon, Latvia, San Diego, Our company will continue to adhere to the " superior quality, reputable, the user first " principle wholeheartedly. We warmly welcome friends from all walks of life to visit and give guidance, work together and create a brilliant future!
  • This supplier stick to the principle of "Quality first, Honesty as base", it is absolutely to be trust.
    5 Stars By Chris from USA - 2017.08.21 14:13
    This company has a lot of ready-made options to choose and also could custom new program according to our demand, which is very nice to meet our needs.
    5 Stars By Marguerite from Bogota - 2018.06.09 12:42
    Write your message here and send it to us