Main Parameters And Technical Performance
● The main technical performance indicators and component equipment of the starter (see Table 1);
● The starter rated control circuit voltage Us is: AC 50/60Hz, 24V, 42V, 110V, 220/230V, 240V,
380/400V, 415V, 440V, 480V, 6OOV;
● Range of action:
○ Pull-in voltage: 50 or 60H 80%Us-110% Us; 50/60Hz 85%Us~110%Us;
○ Release voltage: 20%Us-75%Us
● The operating range of the starter with thermal (overload) relay has the operating characteristics
of thermal relay;
5. The operating frequency with thermal relay is 30 times/hour;
Technical Parameters
Type |
Maximum power AC3 duty(KW) |
Rated current(A) |
Type of enclosure |
Suitable Thermal Relay(A) |
|||||
220V 230V |
380V 400V |
415V |
440V |
500V |
660V 690V |
||||
JLE1-D09 |
2.2 |
4 |
4 |
4 |
5.5 |
5.5 |
9 |
IP42 IP65 |
JLR2-D1312 JLR2-D1314 |
JLE1-D12 |
3 |
5.5 |
5.5 |
5.5 |
7.5 |
7.5 |
12 |
IP42 IP55 |
JLR2-D1316 |
JLE1-D18 |
4 |
7.5 |
9 |
9 |
10 |
10 |
18 |
IP42 IP55 |
JLR2-D1321 |
JLE1-D25 |
5.5 |
11 |
11 |
11 |
15 |
15 |
25 |
IP42 IP55 |
JLR2-D1322 JLR2-D2353 |
JLE1-D32 |
7.5 |
15 |
15 |
15 |
18.5 |
18.5 |
32 |
IP55 |
JLR2-D2355 |
JLE1-D40 |
11 |
18.5 |
22 |
22 |
22 |
30 |
40 |
IP55 |
JLR2-D3353 JLR2-D3355 |
JLE1-D50 |
15 |
22 |
25 |
30 |
30 |
33 |
50 |
IP55 |
JLR2-D3357 JLR2-D3359 |
JLE1-D65 |
18.5 |
30 |
37 |
37 |
37 |
37 |
65 |
IP55 |
JLR2-D3361 |
JLE1-D80 |
22 |
37 |
45 |
45 |
55 |
45 |
80 |
IP55 |
JLR2-D3363 JLR2-D3365 |
JLE1-D95 |
25 |
45 |
45 |
45 |
55 |
45 |
95 |
IP55 |
JLR2-D3365 |
Enclosure |
LE1-D09 and D12 |
Double insulated, protexted to IP 429(3) or to IP 659(4) |
|||||||
LE1-D18 and D25 |
Double insulated, protexted to IP 427(3) or to IP 557(4) |
||||||||
LE1-D32…D95 |
Metal, IP 55 to IP 559 |
||||||||
Control(2 pushbuttons mounted on enclosure cover) |
LE1-D09…D95 |
1 green Start button “I” 1red Stop/Reset button”O” |
|||||||
Connections |
LE1-D32…D95 |
Pre-wired power and control circuit connections |
|||||||
Standard control circuit voltages |
|||||||||
Volts |
24 |
42 |
48 |
110 |
220/230 |
230 |
240 |
380/400 |
440 |
50/60HZ |
B7 |
D7 |
E7 |
F7 |
M7 |
P7 |
U7 |
Q7 |
R |
Shape And Installation Dimensions(mm)
Product detail pictures:
Related Product Guide:
Our pursuit and firm aim should be to "Always fulfill our buyer requirements". We carry on to produce and structure top-quality excellent solutions for equally our aged and new consumers and accomplish a win-win prospect for our consumers as well as us for OEM manufacturer Ac3 Contactor - Magnetic Starter LE1 Series – JUHONG , The product will supply to all over the world, such as: Estonia, Turkey, Mumbai, We'd like to invite customers from abroad to discuss business with us. We can present our clients with high quality products and excellent service. We're sure that we'll have good cooperative relationships and make a brilliant future for both parties.
By Alma from Mozambique - 2017.05.21 12:31
The after-sale warranty service is timely and thoughtful, encounter problems can be resolved very quickly, we feel reliable and secure.
By Lynn from Palestine - 2017.12.02 14:11