Technical Characteristic
Type | Rated current of trip unit In(A) | Setting current adjustment range (A) | Rated ultimate short-circuit breaking capacity lcu (kA), rated operating short-circuit breaking capacity lcs (kA) | Arcing distance (mm) | |||||||||
230/240V | 400/415V | 440V | 500V | 690V | |||||||||
Icu | Ics | Icu | Ics |
Icu |
Ics | Icu | Ics | Icu | Ics | ||||
0.16 |
0.1-0.16 |
100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 100 | 100 |
40 |
|
0.25 |
0.16-0.25 |
100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 100 | 100 |
40 |
|
JGV2-32 | 0.4 |
0.25-0.4 |
100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 100 | 100 |
40 |
0.63 |
0.4-0.63 |
100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 100 | 100 |
40 |
|
1 | 0.63-1 | 100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 100 | 100 |
40 |
|
1.6 | 1-1.6 | 100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 100 | 100 |
40 |
|
2.5 | 1.6-2.5 | 100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 3 | 2.25 |
40 |
|
4 | 2.5-4 | 100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 3 | 2.25 |
40 |
|
6.3 | 4-6.3 | 100 | 100 | 100 | 100 |
50 |
50 | 50 | 50 | 3 | 2.25 |
40 |
|
10 | 6-10 | 100 | 100 | 100 | 100 |
15 |
15 | 10 | 10 | 3 | 2.25 |
40 |
|
14 | 9-14 | 100 | 100 | 15 | 7.5 |
8 |
4 | 6 | 4.5 | 3 | 2.25 |
40 |
|
18 | 13-18 | 100 | 100 | 15 | 7.5 |
8 |
4 | 6 | 4.5 | 3 | 2.25 |
40 |
|
23 | 17-23 | 50 | 50 | 15 | 6 |
6 |
3 | 4 | 3 | 3 | 2.25 |
40 |
|
32 | 24-32 | 50 | 50 | 15 | 6 |
6 |
3 | 4 | 3 | 3 | 2.25 |
40 |
|
JGV3-80 | 40 | 25-40 | - | - | 35 | 17.5 | - | - | - | - | 4 | 2 |
50 |
63 | 40-63 | - | - | 35 | 17.5 | - | - | - | - | 4 | 2 |
50 |
|
80 | 56-80 | - | - | 35 | 17.5 | - | - | - | - | 4 | 2 |
50 |
Rated power of the three-phase motor controlled by the circuit breaker (see Table 2)
The enclosure protection level is: IP20;
The operating performance of the circuit breaker (see Table 3)
Type | Frame rated current Inm(A) | Operating cycles per hour | Operation cycle times | ||
Power ups | No power | Total | |||
1 | 32 | 120 | 2000 | 10000 | 12000 |
2 | 80 | 120 | 2000 | 10000 | 12000 |
Outline and Mounting Dimension
Product detail pictures:
Related Product Guide:
We always believe that one's character decides products' quality, the details decides products' quality ,with the REALISTIC,EFFICIENT AND INNOVATIVE team spirit for OEM Factory for Schneider Circuit Breaker - Motor Protector With Overload Protection JGV2 – JUHONG , The product will supply to all over the world, such as: Afghanistan, Zambia, Amman, Whether selecting a current product from our catalog or seeking engineering assistance for your application, you can talk to our customer service center about your sourcing requirements. We can provided good quality with competitive price for you.
By Althea from Nigeria - 2017.05.21 12:31
We have been cooperated with this company for many years, the company always ensure timely delivery ,good quality and correct number, we are good partners.
By Hilary from Uruguay - 2018.09.16 11:31
Write your message here and send it to us