Technical Characteristic
Type | Rated current of trip unit In(A) | Setting current adjustment range (A) | Rated ultimate short-circuit breaking capacity lcu (kA), rated operating short-circuit breaking capacity lcs (kA) | Arcing distance (mm) | |||||||||
230/240V | 400/415V | 440V | 500V | 690V | |||||||||
Icu | Ics | Icu | Ics |
Icu |
Ics | Icu | Ics | Icu | Ics | ||||
0.16 |
0.1-0.16 |
100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 100 | 100 |
40 |
|
0.25 |
0.16-0.25 |
100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 100 | 100 |
40 |
|
JGV2-32 | 0.4 |
0.25-0.4 |
100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 100 | 100 |
40 |
0.63 |
0.4-0.63 |
100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 100 | 100 |
40 |
|
1 | 0.63-1 | 100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 100 | 100 |
40 |
|
1.6 | 1-1.6 | 100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 100 | 100 |
40 |
|
2.5 | 1.6-2.5 | 100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 3 | 2.25 |
40 |
|
4 | 2.5-4 | 100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 3 | 2.25 |
40 |
|
6.3 | 4-6.3 | 100 | 100 | 100 | 100 |
50 |
50 | 50 | 50 | 3 | 2.25 |
40 |
|
10 | 6-10 | 100 | 100 | 100 | 100 |
15 |
15 | 10 | 10 | 3 | 2.25 |
40 |
|
14 | 9-14 | 100 | 100 | 15 | 7.5 |
8 |
4 | 6 | 4.5 | 3 | 2.25 |
40 |
|
18 | 13-18 | 100 | 100 | 15 | 7.5 |
8 |
4 | 6 | 4.5 | 3 | 2.25 |
40 |
|
23 | 17-23 | 50 | 50 | 15 | 6 |
6 |
3 | 4 | 3 | 3 | 2.25 |
40 |
|
32 | 24-32 | 50 | 50 | 15 | 6 |
6 |
3 | 4 | 3 | 3 | 2.25 |
40 |
|
JGV3-80 | 40 | 25-40 | - | - | 35 | 17.5 | - | - | - | - | 4 | 2 |
50 |
63 | 40-63 | - | - | 35 | 17.5 | - | - | - | - | 4 | 2 |
50 |
|
80 | 56-80 | - | - | 35 | 17.5 | - | - | - | - | 4 | 2 |
50 |
Rated power of the three-phase motor controlled by the circuit breaker (see Table 2)
Type | Rated current of trip unit In(A) | Rated current adjustment range (A) | Standard rated power of three-phase motor (kW) | |||||
AC-3, 50Hz/60Hz | ||||||||
230/240V |
400V |
415V |
440V |
500V |
690V | |||
0.06 | 0.1-0.16 | - | - | - | - | - | - | |
0.25 | 0.6-0.25 | - | - | - | - | - | - | |
JGV2-32 | 0.4 | 0.25-0.4 | - | - | - | - | - | - |
0.63 | 0.4-0.63 | - | - | - | - | - | 0.37 | |
1 | 0.63-1 | - | - | - |
0.37 |
0.37 |
0.55 | |
1.6 | 1-1.6 | - |
0.37 |
- |
0.55 |
0.75 |
1.1 | |
2.5 | 1.6-2.5 | 0.37 |
0.75 |
0.75 |
1.1 |
1.1 |
1.5 | |
4 | 2.5-4 | 0.75 |
1.5 |
1.5 |
1.5 |
2.2 |
3 | |
6.3 | 4-6.3 | 1.1 |
2.2 |
2.2 | 3 |
3.7 |
4 | |
10 | 6-10 | 2.2 | 4 | 4 | 4 |
5.5 |
7.5 | |
14 | 9-14 | 3 |
5.5 |
5.5 |
7.5 |
7.5 |
9 | |
18 | 13-18 | 4 |
7.5 |
9 | 9 | 9 | 11 | |
23 | 17-23 | 5.5 | 11 | 11 |
11 |
11 | 15 | |
32 | 24-32 | 7.5 | 15 | 15 |
15 |
18.5 |
26 | |
JGV3-80 | 40 | 25-40 | - |
18.5 |
- | - | - | 30 |
63 | 40-63 | - |
30 |
- | - | - | 45 | |
80 | 56-80 | - | 37 | - | - | - | 55 |
The enclosure protection level is: IP20;
The operating performance of the circuit breaker (see Table 3)
Type | Frame rated current Inm(A) | Operating cycles per hour | Operation cycle times | ||
Power ups | No power | Total | |||
1 | 32 | 120 | 2000 | 10000 | 12000 |
2 | 80 | 120 | 2000 | 10000 | 12000 |
Outline and Mounting Dimension
Product detail pictures:
Related Product Guide:
With reliable good quality system, great standing and perfect consumer support, the series of products and solutions produced by our organization are exported to quite a few countries and regions for High definition Schneider Mpcb - GV2-M motor protector with overcurrent protection – JUHONG , The product will supply to all over the world, such as: Portugal, Liberia, Netherlands, Upon today, we have customers from all over the world, including USA, Russia, Spain, Italy, Singapore, Malaysia, Thailand, Poland, Iran and Iraq. The mission of our company is to provide the highest quality products with best price. We are looking forward to doing business with you!
By Jason from Doha - 2018.11.04 10:32
It is a very good, very rare business partners, looking forward to the next more perfect cooperation!
By Mona from Juventus - 2018.10.01 14:14
Write your message here and send it to us