Specification
Type |
Pole |
Rated current (A) |
Rated insulation voltage (V) |
Rated operation voltage (V) |
Arcing-over Distance (mm) |
Ultimate short-circuit Breaking capacity (KA) |
Service short-circuit Breaking capacity (KA) |
Operation performance |
Utilization category |
JM1-63L |
3P/4P |
6,10,16,20,25 32,40,50,63 |
660 |
380 |
0 |
25 |
18 |
1500 |
8500 |
JM1-63M |
660 |
380 |
0 |
50 |
35 |
1500 |
8500 |
||
JM1-100L |
3P/4P |
10,16,20,25,32, |
660 |
380 |
0 |
35 |
22 |
1500 |
8500 |
JM1-100M |
660 |
380 |
≤50 |
50 |
35 |
1500 |
8500 |
||
JM1-100H |
660 |
380 |
≤50 |
85 |
50 |
1000 |
7000 |
||
JM1-225L |
3P/4P |
100, 125, 160, 180, 200, 225 |
660 |
380 |
≤50 |
35 |
22 |
1000 |
7000 |
JM1-225M |
660 |
380 |
≤50 |
50 |
35 |
1000 |
7000 |
||
JM1-225H |
660 |
380 |
≤50 |
85 |
50 |
1000 |
7000 |
||
JM1-400L |
3P/4P |
225, 250, 315, 350, 400 |
660 |
380 |
≤50 |
50 |
35 |
1000 |
4000 |
JM1-400M |
660 |
380 |
≤50 |
65 |
42 |
1000 |
4000 |
||
JM1-400H |
660 |
380 |
≤50 |
65 |
42 |
1000 |
4000 |
||
JM1-630L |
3P |
400, 500, 630 |
660 |
380 |
≤100 |
50 |
35 |
1000 |
4000 |
JM1-630M |
660 |
380 |
≤100 |
65 |
42 |
1000 |
4000 |
||
JM1-630H |
660 |
380 |
≤100 |
65 |
65 |
1000 |
4000 |
||
JM1-800M |
3P |
630, 700, 800 |
660 |
380 |
≤100 |
75 |
50 |
1000 |
4000 |
JM1-800H |
660 |
380 |
≤100 |
100 |
65 |
1000 |
4000 |
||
JM1-1250M |
3P |
1000, 1250 |
660 |
380 |
≤100 |
100 |
65 |
1000 |
4000 |
JM1-1250H |
660 |
380 |
≤100 |
125 |
75 |
1000 |
4000 |
||
JM1-1600M |
3P |
1600 |
660 |
380 |
≤100 |
150 |
80 |
1000 |
4000 |
Note
1.The MCCB has L; M; H types according to their rated limit short-circuit breaking capacity.
2.The MCCB is advantageous for its compact body, high breaking capacity(some even on flying arc), short arc-casting.
3.The MCCB has function of insulation wit its mark
4.The product complies with IEC60947-2, GB14048.2. Type code & signification
5.N-P type from 4-P has 3 types: A type: N-P without current tripper(normally open);
6.B type: N-P without current tripper working together with other 3P;
7.C type: N-P without current tripper working together with other 3P;
8.No code for distribution type breakers, 2 for motor-protection type;
9.No-code for distribution type breakers, 2 for motor-protection type;
It can be divided into L (common) type, M (standard) type and H (high) type. L type with connecting current equal to relevant frame level and M type with breaking capacity equaling to their frame level according to their rated limited short short-circuit breaking capacity (l c u).
10.Normal working situation
11.Altitude 2000m and below;
12.Ambient temperature no higher than+40ºC(45ºC for watercraft)no less than-5ºC;
13.Stand moist air;
14.Stand salty&oil mildew;
15.Most gradient 22.5°;
16.Atmosphere without corrupt&electric air and no danger of explosion;
17.Without rain effect.
Product detail pictures:
Related Product Guide:
We rely upon strategic thinking, constant modernisation in all segments, technological advances and of course upon our employees that directly participate in our success for Good quality Motor Protection Circuit Breaker - Moulded Case Circuit Breaker JM1 – JUHONG , The product will supply to all over the world, such as: Ukraine, Azerbaijan, Albania, We put the product quality and customer's benefits to the first place. Our experienced salesmen supply prompt and efficient service. Quality control group make sure the best quality. We believe quality comes from detail. If you have demand, let us work together to get success.
By Doreen from Kuala Lumpur - 2017.02.14 13:19
It is not easy to find such a professional and responsible provider in today's time. Hope that we can maintain long-term cooperation.
By Joseph from United Kingdom - 2017.07.28 15:46