Excellent quality Mpcb - GV2-M motor protector with overcurrent protection – JUHONG
Excellent quality Mpcb - GV2-M motor protector with overcurrent protection – JUHONG Detail:
Technical Characteristic
Type | Rated current of trip unit In(A) | Setting current adjustment range (A) | Rated ultimate short-circuit breaking capacity lcu (kA), rated operating short-circuit breaking capacity lcs (kA) | Arcing distance (mm) | |||||||||
230/240V | 400/415V | 440V | 500V | 690V | |||||||||
Icu | Ics | Icu | Ics |
Icu |
Ics | Icu | Ics | Icu | Ics | ||||
0.16 |
0.1-0.16 |
100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 100 | 100 |
40 |
|
0.25 |
0.16-0.25 |
100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 100 | 100 |
40 |
|
JGV2-32 | 0.4 |
0.25-0.4 |
100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 100 | 100 |
40 |
0.63 |
0.4-0.63 |
100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 100 | 100 |
40 |
|
1 | 0.63-1 | 100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 100 | 100 |
40 |
|
1.6 | 1-1.6 | 100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 100 | 100 |
40 |
|
2.5 | 1.6-2.5 | 100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 3 | 2.25 |
40 |
|
4 | 2.5-4 | 100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 3 | 2.25 |
40 |
|
6.3 | 4-6.3 | 100 | 100 | 100 | 100 |
50 |
50 | 50 | 50 | 3 | 2.25 |
40 |
|
10 | 6-10 | 100 | 100 | 100 | 100 |
15 |
15 | 10 | 10 | 3 | 2.25 |
40 |
|
14 | 9-14 | 100 | 100 | 15 | 7.5 |
8 |
4 | 6 | 4.5 | 3 | 2.25 |
40 |
|
18 | 13-18 | 100 | 100 | 15 | 7.5 |
8 |
4 | 6 | 4.5 | 3 | 2.25 |
40 |
|
23 | 17-23 | 50 | 50 | 15 | 6 |
6 |
3 | 4 | 3 | 3 | 2.25 |
40 |
|
32 | 24-32 | 50 | 50 | 15 | 6 |
6 |
3 | 4 | 3 | 3 | 2.25 |
40 |
|
JGV3-80 | 40 | 25-40 | - | - | 35 | 17.5 | - | - | - | - | 4 | 2 |
50 |
63 | 40-63 | - | - | 35 | 17.5 | - | - | - | - | 4 | 2 |
50 |
|
80 | 56-80 | - | - | 35 | 17.5 | - | - | - | - | 4 | 2 |
50 |
Rated power of the three-phase motor controlled by the circuit breaker (see Table 2)
Type | Rated current of trip unit In(A) | Rated current adjustment range (A) | Standard rated power of three-phase motor (kW) | |||||
AC-3, 50Hz/60Hz | ||||||||
230/240V |
400V |
415V |
440V |
500V |
690V | |||
0.06 | 0.1-0.16 | - | - | - | - | - | - | |
0.25 | 0.6-0.25 | - | - | - | - | - | - | |
JGV2-32 | 0.4 | 0.25-0.4 | - | - | - | - | - | - |
0.63 | 0.4-0.63 | - | - | - | - | - | 0.37 | |
1 | 0.63-1 | - | - | - |
0.37 |
0.37 |
0.55 | |
1.6 | 1-1.6 | - |
0.37 |
- |
0.55 |
0.75 |
1.1 | |
2.5 | 1.6-2.5 | 0.37 |
0.75 |
0.75 |
1.1 |
1.1 |
1.5 | |
4 | 2.5-4 | 0.75 |
1.5 |
1.5 |
1.5 |
2.2 |
3 | |
6.3 | 4-6.3 | 1.1 |
2.2 |
2.2 | 3 |
3.7 |
4 | |
10 | 6-10 | 2.2 | 4 | 4 | 4 |
5.5 |
7.5 | |
14 | 9-14 | 3 |
5.5 |
5.5 |
7.5 |
7.5 |
9 | |
18 | 13-18 | 4 |
7.5 |
9 | 9 | 9 | 11 | |
23 | 17-23 | 5.5 | 11 | 11 |
11 |
11 | 15 | |
32 | 24-32 | 7.5 | 15 | 15 |
15 |
18.5 |
26 | |
JGV3-80 | 40 | 25-40 | - |
18.5 |
- | - | - | 30 |
63 | 40-63 | - |
30 |
- | - | - | 45 | |
80 | 56-80 | - | 37 | - | - | - | 55 |
The enclosure protection level is: IP20;
The operating performance of the circuit breaker (see Table 3)
Type | Frame rated current Inm(A) | Operating cycles per hour | Operation cycle times | ||
Power ups | No power | Total | |||
1 | 32 | 120 | 2000 | 10000 | 12000 |
2 | 80 | 120 | 2000 | 10000 | 12000 |
Outline and Mounting Dimension
Product detail pictures:
Related Product Guide:
With dependable high quality approach, great reputation and excellent customer support, the series of products and solutions produced by our firm are exported to lots of countries and regions for Excellent quality Mpcb - GV2-M motor protector with overcurrent protection – JUHONG , The product will supply to all over the world, such as: Belgium, Nairobi, Angola, With the development and enlargement of mass clients abroad, now we've set up cooperative relationships with many major brands. We've our own factory and also have many reliable and well-cooperated factories in the field. Adhering to the "quality first, customer first, We are provideing high-quality, low-cost items and first-class service to customers. We sincerely hope to establish business relationship with customers from all over the world on the basis of quality, mutually benefit. We welcome OEM projects and designs.
By Liz from Muscat - 2017.11.01 17:04
The factory can meet continuously developing economic and market needs, so that their products are widely recognized and trusted, and that's why we chose this company.
By Elva from Bahrain - 2018.03.03 13:09
Write your message here and send it to us