Discountable price Analog Timer - Motor Protector With Overload Protection JGV2 – JUHONG
Discountable price Analog Timer - Motor Protector With Overload Protection JGV2 – JUHONG Detail:
Technical Characteristic
Type | Rated current of trip unit In(A) | Setting current adjustment range (A) | Rated ultimate short-circuit breaking capacity lcu (kA), rated operating short-circuit breaking capacity lcs (kA) | Arcing distance (mm) | |||||||||
230/240V | 400/415V | 440V | 500V | 690V | |||||||||
Icu | Ics | Icu | Ics |
Icu |
Ics | Icu | Ics | Icu | Ics | ||||
0.16 |
0.1-0.16 |
100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 100 | 100 |
40 |
|
0.25 |
0.16-0.25 |
100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 100 | 100 |
40 |
|
JGV2-32 | 0.4 |
0.25-0.4 |
100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 100 | 100 |
40 |
0.63 |
0.4-0.63 |
100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 100 | 100 |
40 |
|
1 | 0.63-1 | 100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 100 | 100 |
40 |
|
1.6 | 1-1.6 | 100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 100 | 100 |
40 |
|
2.5 | 1.6-2.5 | 100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 3 | 2.25 |
40 |
|
4 | 2.5-4 | 100 | 100 | 100 | 100 |
100 |
100 | 100 | 100 | 3 | 2.25 |
40 |
|
6.3 | 4-6.3 | 100 | 100 | 100 | 100 |
50 |
50 | 50 | 50 | 3 | 2.25 |
40 |
|
10 | 6-10 | 100 | 100 | 100 | 100 |
15 |
15 | 10 | 10 | 3 | 2.25 |
40 |
|
14 | 9-14 | 100 | 100 | 15 | 7.5 |
8 |
4 | 6 | 4.5 | 3 | 2.25 |
40 |
|
18 | 13-18 | 100 | 100 | 15 | 7.5 |
8 |
4 | 6 | 4.5 | 3 | 2.25 |
40 |
|
23 | 17-23 | 50 | 50 | 15 | 6 |
6 |
3 | 4 | 3 | 3 | 2.25 |
40 |
|
32 | 24-32 | 50 | 50 | 15 | 6 |
6 |
3 | 4 | 3 | 3 | 2.25 |
40 |
|
JGV3-80 | 40 | 25-40 | - | - | 35 | 17.5 | - | - | - | - | 4 | 2 |
50 |
63 | 40-63 | - | - | 35 | 17.5 | - | - | - | - | 4 | 2 |
50 |
|
80 | 56-80 | - | - | 35 | 17.5 | - | - | - | - | 4 | 2 |
50 |
Rated power of the three-phase motor controlled by the circuit breaker (see Table 2)
The enclosure protection level is: IP20;
The operating performance of the circuit breaker (see Table 3)
Type | Frame rated current Inm(A) | Operating cycles per hour | Operation cycle times | ||
Power ups | No power | Total | |||
1 | 32 | 120 | 2000 | 10000 | 12000 |
2 | 80 | 120 | 2000 | 10000 | 12000 |
Outline and Mounting Dimension
Product detail pictures:





Related Product Guide:
Well-run devices, expert profits group, and better after-sales companies; We have been also a unified huge family, everybody keep on with the organization worth "unification, determination, tolerance" for Discountable price Analog Timer - Motor Protector With Overload Protection JGV2 – JUHONG , The product will supply to all over the world, such as: Detroit, Botswana, Macedonia, We hope we can establish long-term cooperation with all of the customers. And hope we can improve competitiveness and achieve the win-win situation together with the customers. We sincerely welcome the customers from all over the world to contact us for anything you need!