Capacitor contactor LC1DWK12 63kVAR
Parameter data sheet
Product or Component Type | TeSys LC1D.K
TeSys Deca
|
Product or component type
|
Capacitor duty contactor |
Device short name | LC1DWK |
Device application | Control |
Contactor application | Power factor correction |
Utilisation category | AC-6b |
Poles description | 3P |
power pole contact composition | 3 NO |
Device location in system | Inside delta interruption
Line interruption |
[Ue] rated operational voltage | Power circuit: 690 V AC 50/60 Hz |
Reactive power rating | 35 kvar at 230 V AC 50 Hz 60 °C
63 kvar at 400 V AC 50 Hz 60 °C 67 kvar at 440 V AC 50 Hz 60 °C 104 kvar at 690 V AC 50 Hz 60 °C 30 kvar at 230 V AC 60 Hz 60 °C 60 kvar at 460 V AC 60 Hz 60 °C 80 kvar at 575 V AC 60 Hz 60 °C |
Control circuit type | AC at 50/60 Hz |
[Uc] control circuit voltage | 220 V AC 50/60 Hz |
Auxiliary contact composition | 1 NO + 2 NC instantaneous |
Electrical durability | 300000 cycles at Ue 400 V
200000 cycles at Ue 690 V |
Mounting support | DIN rail
Plate |
Standards | EN/IEC 60947-1
EN/IEC 60947-4-1 IEC 60335-1 |
Product certifications | IECEE CB Scheme
UKCA |
Connections – terminals | Control circuit: screw clamp terminals 1 1…4 mm² – cable stiffness: solid
Control circuit: screw clamp terminals 2 1…4 mm² – cable stiffness: solid Control circuit: screw clamp terminals 1 1…4 mm² – cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 1…4 mm² – cable stiffness: flexible without cable end Control circuit: screw clamp terminals 1 1…4 mm² – cable stiffness: flexible with cable end Control circuit: screw clamp terminals 2 1…2.5 mm² – cable stiffness: flexible with cable end Power circuit: connector 1 4…50 mm² – cable stiffness: solid Power circuit: connector 2 4…25 mm² – cable stiffness: solid Power circuit: connector 1 4…50 mm² – cable stiffness: flexible without cable end Power circuit: connector 2 4…25 mm² – cable stiffness: flexible without cable end Power circuit: connector 1 4…50 mm² – cable stiffness: flexible with cable end Power circuit: connector 2 4…16 mm² – cable stiffness: flexible with cable end |
Tightening torque | Power circuit: 9 N.m – on connector
Control circuit: 1.7 N.m – on screw clamp terminals |
Maximum operating rate | 240 cyc/h |
Auxiliary contacts type | type mechanically linked 1 NO + 2 NC conforming to IEC 60947-5-1 |
IP degree of protection | IP20 front face conforming to IEC 60529 |
Ambient air temperature for
operation |
-5…60 °C |
Ambient air temperature for
storage |
-60…80 °C |
Operating altitude | 0…3000 m |
Height*Width*Depth | 180 mm*55 mm*154 mm |
Net Weight | 1.65kg |